MEDICAL AIR SYSTEM
• Inspected Medical Air source supply for design, installation, location, and identification.
Sizing and Capacity Secondary/Reserve Source
• Inspected Medical Air Intake.
Location Fresh Air Criteria
• Inspected dryers, filters, regulators, and pressure relief valve.
Dryer Capacity versus Demand Regulator Location
Correct Values
• Inspected required source, main, and riser values.
Location/Labeling Valve Handles Locked or Secure
• Tested all area and master alarm functions.
• Inspected proper pressure switch and area alarm sensor locations.
• Tested Medial Air system for gas concentration at source supply and outlets.
Allowable concentrations of 19.5-23.5% oxygen analyzed.
• Tested Medical Air for particulate contamination in at least 25% of zones.
Tested with a 0.45 micron filter device
• Tested source for dew point.
• Tested each Medical Air outlet for proper function, identification, adaptation, and mechanical integrity.
Identified leaking/malfunctioning outlets
Identified outlets delivering substandard pressure/flow rate
• Tested Medical Air zone shut-off zone valves for proper function, identification, and mechanical integrity.
• Checked Medical Air zone valves for proper gas identification labeling.
• Tested Medical Air system for operational pressures of 50-55 psi at each zone.
• Tested each outlet for operational pressure and flow rates.
All outlets shall deliver 3.5 scfm with a pressure drop of not more than 5 psi and
static pressure of 50-55 psi.
Critical Care outlets shall permit a transient flow rate of 6 scfm for 3 seconds.
• Tested Medical Air system components for leakage.
• Checked Medical Air system components for proper installation (i.e.: Brazing, Labeling,
Hanging, etc.)
• Checked for cross-connections.
|